TS700 LEC Installation
The TS700 LEC (Local Expansion Card) is
connected to the “Remote Network” and provides
two additional programmable detection circuits
and a programmable output. The “Remote
Network” may have up to three LECs connected,
as the system will always require at least one
remote keypad.
Always ensure that all power (mains
and battery) is removed before
making any connections to the LEC.
1. Remove the cover from the base and carefully
remove the PCB.
2. If the LEC is being fitted inside the control panel
you may remove the LEC PCB from its base
and secure it to base of the control panel using
self adhesive feet. If required, the tamper
switch may also be disabled by fitting the
jumper link across JP2, see Figure 12.
3. If the LEC is being fitted outside the control
panel, hold the base in position and mark the
two securing holes. Drill and plug the wall, then
pass all cables into the base via the cable
entry points. Secure the base to the wall using
the appropriate fixing screws.
4. Connect “Remote Network” cables and
detection circuit cables to the appropriate
terminals, see Figure 12.
5. Set the I/D selector jumper link to the required
position:
I/D Selector Circuit A Circuit B
Panel
Output
109105
211126
313147
415168
NULL N/A N/A N/A
l
No two LECs or remote keypads should
have the same I/D.
l
DO NOT set the I/D selector to the “NULL”
position.
6. Finally clip the LEC cover onto the base being
careful not to trap any cables or to obstruct the
tamper switch.
Wiring Detection Circuits
All detection circuits may be wired as "End Of Line"
(EOL) or "Double Pole" (DP). Both methods can be
used on the same equipment.
Double Pole
The DP method requires the following:
l
The detector alarm and tamper contacts are
connected to the zone and tamper terminals
respectively.
l
The combined alarm and tamper loop
resistance must be less than 100 Ohms.
l
The maximum number of detection devices
allowed in a circuit is ten.
l
Normally open devices such as pressure pads
and exit terminator buttons are connected
between the zone and tamper terminals.
l
If the detection circuit is not used links can be
fitted across the zone and tamper loops or
programmed as Not Used.
12
System Installation TS790 & TS900 Installation Manual
Network
connections
Programmable
output
switched -ve
@100mA
Tamper switch
Fit jumper-link to
disable tamper switch
CABLE ENTRY
CABLE ENTRY
Programmable
detection circuits
I/D selector
CCT B
ED
C
B
LEC I/D
A
12 34
NULL
JP2
TAMPER = JP2 NOT FITTED
NO TAMPER = JP2 FITTED
CCT A
TA
TB
ZA
ZB
O/P
Figure 12. TS700 LEC Layout